Mitsubishi Electric error codes and flashing lights explained

Most Mitsubishi Electric wall units don't show a code on a screen. Instead, the operation indicator lamp flashes a set number of times. Here is how to count the flashes, what each pattern means according to Mitsubishi Electric's service manuals, the codes ducted and cassette systems show, and when to call an engineer.

Slim white wall-mounted air conditioning unit above a sideboard in a Victorian dining room
pause between groups of flashes
2.5 seconds
to be sure of the number
Count twice
diagnostic visit, deducted
£125
we repair systems others installed
Any fitter

How to read the flashing lamp on a wall unit

  1. Spot the fault

    The indoor fan stops and the operation indicator lamp on the front of the indoor unit starts flashing.

  2. Count the flashes

    Flashes come half a second apart, then the lamp goes off for about 2.5 seconds before the group repeats. Count two full groups to be sure.

  3. Check for even flashing

    If the lamp flashes on and off evenly with no long pause, that's a different fault: the first row in the table below.

  4. Write it down

    Note the number of flashes and the model number from the label on the side of the indoor unit.

What the flashes mean on MSZ-LN and MSZ-AP wall units

Mitsubishi Electric's troubleshooting table, in plain English. On the MSZ-LN it's the POWER lamp; on the MSZ-AP, the upper lamp.

Lamp patternWhat Mitsubishi Electric says it meansWhat you can do
Flashing evenly, no pauseNo signal from the outdoor unit for 6 minutes: a wiring or communication faultDo one power reset at the isolator. If it comes back, the wiring or a circuit board needs checking.
2 flashesIndoor coil sensor or room temperature sensor open or short circuitBook an engineer to test the sensors.
3 flashesIndoor fan motor fault: no speed signal while the fan runsBook an engineer. Don't try to turn the fan by hand.
4 flashesIndoor circuit board can't read its memoryBook an engineer. The usual fix is a new indoor circuit board.
5 flashesCompressor stopped on overcurrent or failed to start 3 times within a minute of startingBook an engineer. The checks include the refrigerant valves, the compressor and the inverter.
6 flashesOutdoor unit temperature sensor open or short circuitBook an engineer.
7 flashesOutdoor circuit board can't read its memoryBook an engineer.
14 flashes or moreAnother outdoor fault, which the engineer reads at the outdoor unitBook an engineer. The checks include the refrigerant valves and the 4-way valve.
Lamp lit steadily, outdoor unit not runningOutdoor circuit board can't read its memoryBook an engineer.

Source: Mitsubishi Electric service manuals OBH766 (MSZ-LN-VG) and OBH788 (MSZ-AP-VG), troubleshooting check table, checked October 2026.

Multi-split: one room won't start

On a multi-split, a room that won't start isn't always a fault. Mitsubishi Electric's manuals say that if one room is set to cooling or dry and another to heating, the room switched on first takes priority. Set every room to the same mode and the waiting unit should start.

Check codes on ducted and cassette systems

Ducted and ceiling cassette units on an SUZ outdoor unit show a check code on the wired controller. With a wireless remote, the self-check reports it as a number of beeps and flashes.

Wired codeWireless flashesMeaningWhat you can do
P11Room air (intake) sensor errorBook an engineer.
P2, P92Pipe temperature sensor errorBook an engineer.
E6, E73Indoor and outdoor units can't communicateOne power reset. Book an engineer if it returns.
P44Drain sensor error, or the float switch connector is openBook an engineer.
P55Drain pump errorSwitch off if water is leaking and book an engineer.
PA5Compressor forced to stop because of a water leakage problemSwitch off, keep the area dry and book an engineer.
P66Freezing or overheating protectionClean the filters and clear the airflow. Book us if it returns.
EE7Indoor and outdoor units don't matchBook an engineer.
E4, E59Remote controller signal receiving errorBook an engineer.
Fb12Indoor unit control board errorBook an engineer.
PL14Abnormality in the refrigerant circuitBook an F-Gas certified engineer.
UP2, outdoorCompressor overcurrent cut-outBook an engineer.
U3, U43, outdoorOutdoor unit temperature sensor open or shortBook an engineer.
E91, outdoorOutdoor unit can't send its signal to the indoor unitOne power reset. Book an engineer if it returns.

Source: Mitsubishi Electric SUZ-M technical and service manual OCH684G. For outdoor faults, the lamp stays on for about 3 seconds before each group of flashes.

Safe checks before you book

Anyone can do these safely. If the same pattern comes back, stop resetting and book a visit.

  • Write down the number of flashes and the model number from the indoor unit's label
  • Check the remote's batteries, and that it's set to the mode you want
  • Switch off, then clean the air filters behind the front panel
  • Clear leaves, bins or covers from around the outdoor unit, keeping hands away from the fan
  • Do one power reset: switch off at the isolator or breaker, wait a few minutes, then switch on

What a Mitsubishi Electric repair visit costs

The diagnostic visit covers the first hour on site and comes off the bill if you go ahead. We repair Mitsubishi Electric wall, ducted and cassette systems whoever installed them.

  • Repair diagnostic visit

    First hour on site, deducted if you go ahead

    from£125inc. VAT

Mitsubishi Electric error code questions

Why is the light flashing on my Mitsubishi Electric air conditioner?

It means the unit has found a fault and stopped the indoor fan. The number of flashes in each group tells you which fault. Count two full groups, then check the table above.

What does 5 flashes mean on a Mitsubishi Electric wall unit?

On the MSZ-LN and MSZ-AP, 5 flashes means the compressor has stopped for overcurrent, or failed to start, 3 times within a minute of starting. Mitsubishi Electric's checks include the refrigerant valves, the compressor and the inverter, so it needs an engineer.

What does E6 mean on a Mitsubishi Electric controller?

On ducted and cassette systems with an SUZ outdoor unit, E6 or E7 means the indoor and outdoor units can't communicate. Try one power reset at the isolator. If the code comes back, book an engineer to check the wiring and circuit boards.

Can an engineer see past faults on a Mitsubishi Electric unit?

Yes. Mitsubishi Electric wall units remember the last fault even after the lamp stops flashing. An engineer can recall it with a set-up sequence on the remote, so it's worth mentioning a fault that cleared by itself.