Mitsubishi Electric error codes: what the flashing light means
Mitsubishi Electric home units don't show a code on a screen. Instead, the operation indicator lamp blinks a set number of times. Here is how to count the blinks, what each pattern means according to Mitsubishi Electric's own service manuals, what you can safely check, and when to book an engineer.

- pause between groups of blinks
- 2.5 seconds
- Mitsubishi's advice for a sure count
- Count twice
- repair price before any work
- Written
- we repair systems others installed
- Any fitter
On this page11 sections
How a Mitsubishi Electric shows a fault
When a Mitsubishi Electric home unit finds a fault, the indoor fan stops and the operation indicator lamp blinks. The number of blinks in each group points to the area of the fault.
- MSZ-LN: the POWER lamp blinks
- MSZ-AP: the upper lamp
- MSZ-HR: the left lamp (upper on the larger HR60 and HR71)
- MFZ-KT floor unit: the left lamp
- The unit remembers the last fault after the lamp stops blinking, and an engineer can recall it with a set-up sequence on the remote
- So it's worth mentioning a fault that cleared by itself
How to read the blinking lamp
Spot the fault
The indoor fan stops and the lamp on the front of the indoor unit starts blinking.
Count the blinks
Blinks come half a second apart. Then the lamp goes off for about 2.5 seconds before the group repeats. A phone video makes counting easier.
Count two groups
Mitsubishi Electric's manuals say to check at least two full cycles before deciding the number.
Check for even blinking
If the lamp blinks on and off evenly with no long pause, that's the communication fault in the first row of the table below.
Note the model number
Photograph the label on the side of the indoor unit, and the outdoor unit's label too if you can see it safely.
What the blinks mean on wall and floor units
Mitsubishi Electric's troubleshooting check table for MSZ-LN, MSZ-AP, MSZ-HR and MFZ-KT units, in plain English.
| Lamp pattern | What it means | What you can safely do | When to book |
|---|---|---|---|
| Blinking evenly, no pause | No signal from the outdoor unit for 6 minutes: a wiring or communication fault | Check the breaker. One power reset at the isolator | If it comes back: the wiring or a board needs checking |
| 2 blinks | Indoor coil sensor or room temperature sensor open or short circuit | Note the pattern and switch off | Now: the sensors need testing |
| 3 blinks | Indoor fan motor fault: no speed signal while the fan runs | Switch off. Don't try to turn the fan by hand | Now |
| 4 blinks | Indoor circuit board can't read its memory | Note the pattern | Now. The usual fix is a new indoor circuit board |
| 5 blinks | Compressor stopped on overcurrent or failed to start 3 times within a minute of starting | Note the pattern and switch off | Now: the checks include the stop valves, compressor and inverter |
| 6 blinks | Outdoor unit temperature sensor open or short circuit | Note the pattern | Now |
| 7 blinks | Outdoor circuit board can't read its memory | Note the pattern | Now. The fix is usually an outdoor or inverter board |
| 14 blinks or more | Another fault, which the engineer identifies with the outdoor fault recall | Note the pattern. Don't restart it again and again | Now: checks include the stop valves, 4-way valve and sensors |
| Lamp lit steadily, outdoor unit not running | Outdoor circuit board can't read its memory | Note it | Now: the engineer reads the LED on the outdoor board |
| Floor unit: left lamp 3 blinks, right lamp on | MFZ-KT refrigerant sensor has detected a leak. The fan runs for 3 hours | Keep flames and sprays away. Switch off at the isolator once the fan stops | Now, with an F-Gas engineer |
| Floor unit: left lamp 2 blinks, right lamp on | MFZ-KT refrigerant sensor not working, disconnected or its wire broken | Note the pattern | Now |
Source: Mitsubishi Electric service manuals OBH766H, OBH788, OBH822H and OBH843F, troubleshooting check table, checked October 2026.
Multi-split outdoor faults the engineer reads
On an MXZ multi-split, the engineer puts the remote into fault recall mode and counts the indoor lamp again. These patterns are different from the table above, so don't mix them up. They're here so you know what the engineer is talking about.
| Recall blinks | What it means | When to book |
|---|---|---|
| 2 blinks | Compressor overcurrent cut-out 3 times in a row within a minute of starting | Book a repair |
| 3 blinks | An outdoor temperature sensor open or short circuit | Book a repair |
| 4 blinks | Overcurrent through the power module driving the compressor | Book a repair |
| 5 blinks | Discharge temperature too high, above 116°C on 2-room models | Book an F-Gas engineer: refrigerant amount is among the checks |
| 6 blinks | High pressure: outdoor coil above 70°C in cooling, or indoor gas pipe above 70°C in heating | Book an F-Gas engineer |
| 7 blinks | Inverter fin above 90°C or outdoor board above 80°C. The first check is around the outdoor unit | Clear the outdoor unit's surroundings, then book if it returns |
| 8 blinks | Outdoor fan motor failed 3 times within 30 seconds of starting | Book a repair |
| 9 blinks | Outdoor board memory can't be read, or the power module or compressor winding has shorted | Book a repair |
| 10 blinks | Discharge temperature stays too low for over 40 minutes | Book an F-Gas engineer |
| 11 blinks | Compressor current sensor or supply voltage fault | Book a repair |
| 14 blinks | Stop valve fault, a refrigerant leak sensed indoors, or an indoor unit that isn't compatible | Book an F-Gas engineer |
| 17 blinks | Closed valve or air in the refrigerant circuit detected | Book an F-Gas engineer |
Source: Mitsubishi Electric service manual OBH790P (MXZ-2F, 3F, 4F, 5F and 6F), outdoor unit failure mode recall for 2-room MXZ-2F models, checked October 2026. Larger MXZ models use a similar table with small differences.
Multi-split: one room won't start
On a multi-split, a room that won't start isn't always a fault. Mitsubishi Electric's manuals say that if one room is set to cooling or dry and another to heating, the room switched on first takes priority and the other unit's lamp blinks. Set every room to the same mode and the waiting unit should start.
Mitsubishi Electric's manual also notes that if a unit starts while the outdoor unit is defrosting, warm air can take up to 10 minutes. That's normal in cold weather.
Safe checks before you book
Anyone can do these safely. If the same pattern comes back, stop resetting and book a visit.
- Write down the number of blinks and the model number from the indoor unit's label
- Check the remote's batteries, and that every room on a multi-split is set to the same mode
- Switch off, then clean the air filters behind the front panel, as your user manual shows
- Clear leaves, bins or covers from around the outdoor unit, keeping hands away from the fan
- Do one power reset: switch off with the remote, then at the isolator or breaker, wait a few minutes, switch on
- If a breaker trips again, leave it off and book an engineer
Booking a Mitsubishi Electric repair
We repair Mitsubishi Electric wall, floor and multi-split systems whoever installed them. Tell us the blink pattern, the model number and when it started when you book, and we'll tell you what it usually means before the visit.
We confirm the cost of the visit when you book. On the visit, the engineer reads the stored fault, confirms the cause and gives you a written price for the repair before any work starts. Refrigerant work is done by our F-Gas and REFCOM certified engineers. Visits are booked ahead, not same day.
Mitsubishi Electric error code questions
Why is the light flashing on my Mitsubishi Electric air conditioner?
It means the unit has found a fault and stopped the indoor fan. The number of blinks in each group tells you which area the fault is in. Count two full groups, then check the table above. On a multi-split, a blinking lamp can also mean another room is set to a different mode.
What does 5 flashes mean on a Mitsubishi Electric?
On MSZ-LN, MSZ-AP, MSZ-HR and MFZ-KT units, 5 blinks means the compressor has stopped for overcurrent, or failed to start, 3 times within a minute of starting. Mitsubishi Electric's checks include the stop valves, the compressor and the inverter, so it needs an engineer.
What does 2 flashes mean on a Mitsubishi Electric?
Two blinks means the indoor coil sensor or the room temperature sensor is reading as open or short circuit. It's a sensor or wiring fault inside the indoor unit, so switch off and book an engineer to test the sensors.
Why is the light blinking evenly with no pause?
Even blinking with no long pause means the indoor unit hasn't had a signal from the outdoor unit for 6 minutes. Check the breaker and do one power reset at the isolator. If it comes back, the wiring between the units or a circuit board needs checking.
How do I reset a Mitsubishi Electric air conditioner?
Switch off with the remote, then at the isolator or breaker, wait a few minutes and switch back on. That's the only reset to try yourself, and only once. If the same blink pattern returns, the fault is real and needs an engineer.
Can an engineer see past faults on a Mitsubishi Electric unit?
Yes. Mitsubishi Electric units remember the last fault even after the lamp stops blinking. An engineer recalls it with a set-up sequence on the remote, and on multi-splits can read the outdoor unit's detailed fault the same way.